### CODE INFORMATION
##### Codes
* **General:** _International Building Code (IBC) 2021_ & SPS 361366 Amendments
* **Existing:** _International Existing Building Code (IEBC) 2021_ & SPS 366 Amendments
* **Energy Conservation:** _International Energy Conservation Code (IECC) 2021_ & SPS 363 Amendments
* **Plumbing:** _Wisconsin Plumbing Code:_ SPS 380387
* **Mechanical:** _International Mechanical Code (IMC) 2021_ & SPS 364 Amendments
* **Electrical:**_National Electrical Code (NEC) 2017_ & SPS 316 Amendments
* **Fire:** _International Fire Code (IFC) 2021_ & SPS 314 Amendments
* **Fuel:** _International Fuel Gas Code (IFGC) 2021_ & SPS 365 Amendments
* **Accessibility:** _ANSI Standard A117.12017_ - Accessibility <!-- https://up.codes/viewer/wisconsin/icc-a117.1-2017 -->
<!--
Chapter 35 Referenced Standards: https://up.codes/viewer/wisconsin/ibc-2021/chapter/35/referenced-standards#35 -->
##### [IBC Chapter 3 - Use and Occupancy Classification](https://up.codes/viewer/wisconsin/ibc-2021/chapter/3/occupancy-classification-and-use#3)
* **Scope Area:**
* 310.3 Residential Group R-2
##### [IEBC Chapter 6 - Classification of Work](https://up.codes/viewer/wisconsin/iebc-2021/chapter/6/classification-of-work#6)
* Section 602 Alteration—Level 1 (Portions of the Roof and portions of the Facade)
* Section 603 Alteration—Level 2 (Facade - replacement of windows/doors)
<!-- * Section 604 Alteration—Level 3 -->
<!-- ##### [IBC 504.3 - Height in Feet](https://up.codes/viewer/wisconsin/ibc-2021/chapter/5/general-building-heights-and-areas#504.3)
* **Type V-B (non-Sprinklered):**
* Actual: 30 ft
* Allowed:
* (B): 40 ft
##### [IBC 504.4 - Number of Stories](https://up.codes/viewer/wisconsin/ibc-2021/chapter/5/general-building-heights-and-areas#504.4)
* Actual: 2 story
* Allowed:
* (B): 2 stories
##### [IBC 506.2 - Allowable Area Determination](https://up.codes/viewer/wisconsin/ibc-2021/chapter/5/general-building-heights-and-areas#506.2)
* Actual: 1996 SF
* Allowed:
* (B): 9,000 SF
##### [IBC 508.3 - Nonseparated Occupancies](https://up.codes/viewer/wisconsin/ibc-2015/chapter/5/general-building-heights-and-areas#508.3) -->
<!-- * No (not in immediate scope) -->
<!-- ##### [IBC 508.4 - Separated Occupancies](https://up.codes/viewer/wisconsin/ibc-2021/chapter/5/general-building-heights-and-areas#508.4)
* Yes
* Required Separation per Table 508.4: N = No separation requirement -->
##### [IBC Table 601 - Fire-resistance Rating Requirements For Building Elements (Hours)](https://up.codes/viewer/wisconsin/ibc-2021/chapter/6/types-of-construction#601)
* **Type VB:**
* Structural Frame: 0 hr
* Bearing Walls (Exterior/Interior): 0 hr
* Non-Bearing Walls (Interior): 0 hr
* Floors: 0 hr
* Roof: 0 hr
##### [IBC Section 602 - Construction Classification](https://up.codes/viewer/wisconsin/ibc-2021/chapter/6/types-of-construction#602)
* Type VB
##### [705.5 - Fire-Resistance Ratings](https://up.codes/viewer/wisconsin/ibc-2021/chapter/7/fire-and-smoke-protection-features#705.5)
* **Type V-B:**
* X < 5 ft: 1 hr
* 5 X 10: 1 hr
* 10 X 30: 0 hr
* X 30: 0 hr
<!--
##### [IBC Section 713 - Shaft Enclosures](https://up.codes/viewer/wisconsin/ibc-2021/chapter/7/fire-and-smoke-protection-features#713.4)
* Shaft enclosures shall have a fire-resistance rating of <!- not less than 2 hours where connecting four stories or more, and -> not less than 1 hour where connecting less than four stories.
-->
<!-- ##### [IBC Table 803.13 - Interior Wall And Ceiling Finish Requirements By Occupancy](https://up.codes/viewer/wisconsin/ibc-2021/chapter/8/interior-finishes#table_803.13)
* **(B) NONSPRINKLERED**
* Exit Stairways/Ramps: Class A
* Corridors: Class B
* Rooms/Enclosures: Class C -->
<!--
Class A, B, C:
https://up.codes/viewer/wisconsin/ibc-2021/chapter/8/interior-finishes#803.1.2
-->
##### [IBC Section 903 - Automatic Sprinkler Systems](https://up.codes/viewer/wisconsin/ibc-2021/chapter/9/fire-protection-and-life-safety-systems#903.2)
* Yes for:
* 2117 Red Arrow Trail
* 453 Thurston Lane
* No for:
* 4545 Thurston Lane
* 2113 Red Arrow Trail
<!-- * Sprinklers per NFPA 13 -->
<!-- * No Sprinklers -->
<!-- ##### [IBC Section 906 - Portable Fire Extinguishers](https://up.codes/viewer/wisconsin/ibc-2021/chapter/9/fire-protection-and-life-safety-systems#906.3)
* **Ordinary (Moderate) Hazard Occupancy:**
* Type 2-A:
* Maximum floor area per unit of A: 1,500 SF
* Maximum floor area for extinguisher: 75 ft
* Maximum floor area for extinguisher: 11,250 sf
* Max distance to extinguisher: 75 ft -->
<!-- * **Commercial Kitchens (if applicable):**
* Type 2-A:K extinguisher (2.5-gal or two 1.5-gal within 30 ft) -->
<!--
The (3) Occupancy Hazards
5.4.1 Classifying Occupancy Hazard. R
https://www.edufire.ir/storage/Library/ETFA-ABI/NFPA/NFPA%2010-2022.pdf
-->
##### [IBC Section 907 - Fire Alarm and Detection Systems](https://up.codes/viewer/wisconsin/ibc-2021/chapter/9/fire-protection-and-life-safety-systems#907.2)
<!-- * No alarm required or provided -->
* A manual fire alarm system is required and is currently provided
<!-- * New alarms to integrate with existing system (design/build per 3rd party). -->
<!-- ##### [IBC Section 1004 - Occupant Load](https://up.codes/viewer/wisconsin/ibc-2021/chapter/10/means-of-egress#table_1004.5)
* See occupant load room schedule -->
<!-- ##### [IBC Table 1020.2 - Corridor Fire-resistance Rating](https://up.codes/viewer/wisconsin/ibc-2021/chapter/10/means-of-egress#table_1020.2)
* For Group B: Not rated with sprinkler system
* If Occupant Load Served by Corridor is greater than 30: 1hr rated
* otherwise: not rated -->
<!-- ##### [IBC 1006.2.1 - Egress Based on Occupant Load and Common Path of Egress Travel Distance](https://up.codes/viewer/wisconsin/ibc-2021/chapter/10/means-of-egress#1006.2.1)
* **Group B (Without Sprinkler):**
* Common Path Travel Distance
* If ≤ 30: 100 ft
* If > 30: 75 ft
* Max occupant load (one exit): 49 -->
<!-- ##### [IBC Table 1006.3.4(2) - Stories With One Exit Or Access To One Exit For Other Occupancies](https://up.codes/viewer/wisconsin/ibc-2021/chapter/10/means-of-egress#table_1006.3.4-2)
* **Group B (Without Sprinkler):**
* Maximum Occupant Load Per Story: 49
* Maximum Exit Access Travel Distance: 75 ft -->
<!-- ##### [IBC Table 1017.2 - Exit Access Travel Distance](https://up.codes/viewer/wisconsin/ibc-2021/chapter/10/means-of-egress#1017.2)
* **Group B (With Sprinkler):**
* Exit Access Travel Distance: 200 ft -->
<!-- ##### [IBC 1020.5 - Dead Ends](https://up.codes/viewer/wisconsin/ibc-2021/chapter/10/means-of-egress#1020.5) -->
<!-- * 20 ft (Without Sprinkler) -->
<!-- * 50 ft (With Sprinkler) -->
<!-- ##### [IEBC Section 808 - Plumbing](https://up.codes/viewer/wisconsin/iebc-2021/chapter/8/alterations-level-2#808) -->
<!-- - Existing restrooms to remain - No occupant load increase -->
<!--
##### [IBC 2902.1 - Minimum Number of Fixtures](https://up.codes/viewer/wisconsin/ibc-2021/chapter/29/plumbing-systems#2902.1) -->
<!--
* **Occupancy M (most stringent) | Total Occupants: 13 (25 Female / 25 Male)**
* [Single Facility](https://up.codes/viewer/wisconsin/ibc-2021/chapter/29/plumbing-systems#2902.2)
* Per section 2902.2 separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 100 or fewer.
* Separate facilities shall not be required in (B) occupancies in which the maximum occupant load is 25 or fewer.
* Water Closets: 1 per 500 → 1 required / 1 provided
* Lavatories: 1 per 750 → 1 required / 1 provided
* Female:
* Water Closets: 1 per 25 → 1 required / 1 provided
* Lavatories: 1 per 40 → 1 required / 1 provided
* Male:
* Water Closets: 1 per 25 → 1 required / 1 provided
* Lavatories: 1 per 40 → 1 required / 1 provided
* Drinking Fountains:
* Water provided by bottle fillers, bottled water, or bar service per [SPS 362.2902(1)(a)2](https://docs.legis.wisconsin.gov/code/admin_code/sps/safety_and_buildings_and_environment/361_366/362/2902/1/a/2)
* Service Sink:
* 1 required / 1 provided
##### IBC Chapter 4 - Special Detailed Requirements
* **Section 420 Groups R-2:**
* Fire Partitions per Section 708
* Horizontal Assemblies per Section 711
##### IBC 708.3 - Fire-Resistance Rating
* Corridors: 0 hr rated
##### IBC 711.2.4.3 - Dwelling Units
* Between dwelling units: ½ hr rated
<!-- PAGE_BREAK -->
##### [IBC Section 1021 - Egress Balconies](https://up.codes/viewer/wisconsin/ibc-2015/chapter/10/means-of-egress#1021)
Exterior egress balconies shall comply with corridor wall requirements per Table 1020.1 and Section 708.
-->
<!--
## **IEBC References**
##### [IEBC 805.6 - Dead-End Corridors](https://up.codes/viewer/wisconsin/iebc-2015/chapter/8/alterations-level-2#805.6)
* 50 feet max
##### [IEBC 810.1 - Minimum Fixtures](https://up.codes/viewer/wisconsin/iebc-2015/chapter/8/alterations-level-2#810.1)
* Occupant load increase <20%
* No change in plumbing fixture count required
##### IPC 410.4 - Water Fountain Substitution
* Water fountain not required per IPC 410.4
##### [IFC Chapter 32 - High-Piled Combustible Storage (3206.2)](https://up.codes/viewer/wisconsin/ifc-2015/chapter/32/high-piled-combustible-storage#table_3206.2)
* **Commodity Class:** IIV
* **Limitations:**
* Max storage area: 12,000 SF (nonpublic)
* Fire extinguishing system: Yes (Section 3206.4)
* Fire detection system: Not required (existing in place)
* Building access / smoke removal: No
* Max pile dimension: 100 ft
* Max storage height: 40 ft
* Max pile volume: 400,000 CF
##### [IFC 3206.9 - Aisles](https://up.codes/viewer/wisconsin/ifc-2015/chapter/32/high-piled-combustible-storage#3206.9)
* In sprinklered buildings: ≥44 inches wide
-->