CODE INFORMATION
Codes
- General: International Building Code (IBC) 2021 & SPS 361–366 Amendments
- Existing: International Existing Building Code (IEBC) 2021 & SPS 366 Amendments
- Energy Conservation: International Energy Conservation Code (IECC) 2021 & SPS 363 Amendments
- Plumbing: Wisconsin Plumbing Code: SPS 380–387
- Mechanical: International Mechanical Code (IMC) 2021 & SPS 364 Amendments
- Electrical:National Electrical Code (NEC) 2017 & SPS 316 Amendments
- Fire: International Fire Code (IFC) 2021 & SPS 314 Amendments
- Fuel: International Fuel Gas Code (IFGC) 2021 & SPS 365 Amendments
- Accessibility: ANSI Standard A117.1–2017 - Accessibility
IBC Chapter 3 - Use and Occupancy Classification
- Scope Area:
- 310.3 Residential Group R-2
IEBC Chapter 6 - Classification of Work
- Section 602 Alteration—Level 1 (Portions of the Roof and portions of the Facade)
- Section 603 Alteration—Level 2 (Facade - replacement of windows/doors)
IBC Table 601 - Fire-resistance Rating Requirements For Building Elements (Hours)
- Type VB:
- Structural Frame: 0 hr
- Bearing Walls (Exterior/Interior): 0 hr
- Non-Bearing Walls (Interior): 0 hr
- Floors: 0 hr
- Roof: 0 hr
IBC Section 602 - Construction Classification
- Type VB
705.5 - Fire-Resistance Ratings
- Type V-B:
- X < 5 ft: 1 hr
- 5 ≤ X ≤ 10: 1 hr
- 10 ≤ X ≤ 30: 0 hr
- X ≥ 30: 0 hr
IBC Section 903 - Automatic Sprinkler Systems
- Yes for:
- 2117 Red Arrow Trail
- 453 Thurston Lane
- No for:
- 4545 Thurston Lane
- 2113 Red Arrow Trail
IBC Section 907 - Fire Alarm and Detection Systems
- A manual fire alarm system is required and is currently provided
IBC Section 1021 - Egress Balconies
Exterior egress balconies shall comply with corridor wall requirements per Table 1020.1 and Section 708. -->