2Applicable Codes:
3General:Building/Dwelling Code IBC 2009 (WI Commercial Building Code SPS 362)
4Existing:International Existing Building Code 2009 (WI Commercial Building Code SPS 366)
5Energy Conservation:International Energy Conservation Code 2009 (WI Commercial Building Code v363)
6Plumbing:International Plumbing Code (WI Commercial Building Code SPS 381-387)
7Mechanical:Mechanical Code IMC 2009 (WI Commercial Building Code SPS 364)
8ElectricalElectrical Code NEC 2008(WI Commercial Building Code SPS 316
9Fire:Fire/Life Safety Code 2009 NFPA-1 (WI Commercial Building Code SPS 314 & 330)
10Accessibility:ANSI Standard A117.1-2009- for Accessibility (WI Commercial Building Code SPS 362)
11Fuel:International Fuel Gas Code 2009 (WI Commercial Building Code Chapter 365)
12Sprinklers:Nohttps://up.codes/viewer/alabama/int_building_code_2009/chapter/9/fire-protection-systems#903
13Basement:No Basement
14Alteration Level (IEBC 405):Level 2https://up.codes/viewer/pennsylvania/int_ebc_2009/chapter/4/classification-of-work#404
15Occupancy Types (302.1):Factory Industrial F-2 Low-Hazard Occupancyhttps://up.codes/viewer/alabama/int_building_code_2009/chapter/3/use-and-occupancy-classification#302
16Business Group B
17Type of Construction:TYPE III-Bhttps://up.codes/viewer/alabama/int_building_code_2009/chapter/6/types-of-construction#602
18Number of Stories1 Story (w/ Mezzanine)
19SECTION 506 BUILDING AREA MODIFICATIONShttps://up.codes/viewer/alabama/int_building_code_2009/chapter/5/general-building-heights-and-areas#506
20Building perimeter lengths (ft)Distance to property line or to far side of R.O.W. (ft)
21facing north: 43160+
22facing east:25060+
23facing south:43160+
24facing west:12317
257941
264960+
27
28Allowable Areas and Heights Type IIIB Factory (F-2) Occupancy
29Allowable area per floor:41249 sq.ft.
30Total allowable area: 41249 sq.ft.
31Maximum allowable height: 55 ft.
32Maximum allowable stories: 3
33
34Allowable Areas and Heights Type IIIB Business (B) OccupancyAllowable area per floor:31523 sq.ft.
35Total allowable area: 31523 sq.ft.
36Maximum allowable height: 55 ft.
37Maximum allowable stories: 3
38TABLE 601- FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (hours)Structural Frame:0 hrhttps://up.codes/viewer/alabama/int_building_code_2009/chapter/6/types-of-construction#602.1
39Bearing Walls- exterior:2 hr
40Bearing Walls-interior:0 hr
41Non-bearing walls-exterior - Fire Separation Distance
42X < 5c = 1 hr
435 = X< 10 = 1 hr
4410 = X< 30 = 1 hr
45X = 30 = 0 hr
46Non-bearing walls-interior:0 hr
47Floor Construction:0 hr
48Roof Construction:0 hr
49
50Corridor Fire Resistance Rating (Table 1018.1)1 hr without Sprinklershttps://up.codes/viewer/alabama/int_building_code_2009/chapter/10/means-of-egress#1018
51Common Path of Egress Travel: (1014.3)75https://up.codes/viewer/alabama/int_building_code_2009/chapter/10/means-of-egress#1014.3
52Maximum Travel Distance: (1016.1)B: 200fthttps://up.codes/viewer/alabama/int_building_code_2009/chapter/10/means-of-egress#1016
53 F-2: 300ft
54Min. number of exits less than 500 (Table 1015.1 & Table 1021.1)2https://up.codes/viewer/alabama/int_building_code_2009/chapter/10/means-of-egress#1015
55Dead end corridor max. lengthExisting (IEBC 805.6): 35fthttps://up.codes/viewer/wyoming/iebc-2015/chapter/8/alterations-level-2#805.6
56New Construction (1018.4): 20fthttps://up.codes/viewer/alabama/ibc-2009/chapter/10/means-of-egress#1018.4
57Fire Extinguishers:Type 2-A: (everywhere except kitchen)https://up.codes/viewer/alabama/ibc-2009/chapter/9/fire-protection-systems#906.3
58Maximum Floor Area Per Unit of A:1,500sf
59Maximum Distance to Extinguisher:75ft
60Hazard Classification:Ordinary (Moderate)
61
62Type K:
632.5-gallon or (2)1.5-gallon
64Maximum Distance to Extinguisher:Within 30ft of cooking equipment
65Hazard Classification:Ordinary (Moderate)