LIGHTING NOTES
  • All bulbs shall be LED with a color temperature as close to 3000K as possible.
  • Emergency illumination shall comply with IBC 1008. The contractor/electrician is responsible for ensuring the following:
    • Refer to the Occupancy Room Schedule to identify spaces requiring emergency lighting. Note that landings outside all major exits also require emergency lighting.
    • Emergency lighting shall provide a minimum of 1 foot-candle throughout all designated spaces.
    • The emergency power system shall supply power for a minimum duration of 90 minutes, using storage batteries, unit equipment, or an on-site generator.
    • Exit signs shall be internally or externally illuminated per IBC 1013.3.
  • If required by the Authority Having Jurisdiction (AHJ), the electrical contractor shall submit plans demonstrating compliance with emergency lighting and energy code requirements. Copies of all approval letters must be provided to the architect.