<tspan dy="0em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">LIGHTING NOTES:</tspan>
<tspan dy="1em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">● ALL BULBS AS CLOSE TO 3000K (COLOR TEMP.) AS POSSIBLE</tspan>
<tspan dy="2em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">● ALL BULBS TO BE LED</tspan>
<tspan dy="3em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">● EMERGENCY ILLUMINATION PER IBC 1008 (CONTRACTOR/ELECTRICIAN TO ASSURE THE</tspan>
<tspan dy="4em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">FOLLOWING)</tspan>
<tspan dy="5em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">  ◦ SEE OCCUPANCY ROOM SCHEDULE FOR THOSE SPACES THAT NEED EMERGENCY</tspan>
<tspan dy="6em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">LIGHTING (ILLUMINATION). IN ADDITION, LANDINGS OUTSIDE MAJOR EXITS REQUIRE</tspan>
<tspan dy="7em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">EMERGENCY LIGHTING AS WELL.</tspan>
<tspan dy="8em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">  ◦ EMERGENCY LIGHTING TO BE A MINIMUM 1 FOOT CANDLE THROUGHOUT DESIGNATED</tspan>
<tspan dy="9em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">SPACES.</tspan>
<tspan dy="10em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">  ◦ THE EMERGENCY POWER SYSTEM SHALL PROVIDE POWER FOR A DURATION OF NOT</tspan>
<tspan dy="11em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">LESS THAN 90 MINUTES AND SHALL CONSIST OF STORAGE BATTERIES, UNIT EQUIPMENT</tspan>
<tspan dy="12em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">OR AN ON-SITE GENERATOR.</tspan>
<tspan dy="13em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">  ◦ EXIT SIGNS SHALL BE INTERNALLY OR EXTERNALLY ILLUMINATED PER IBC 1013.3</tspan>
<tspan dy="14em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">● IF THE AUTHORITY HAVING JURISDICTION (AHJ) REQUIRES IT, THE ELECTRICAL</tspan>
<tspan dy="15em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">CONTRACTOR MUST SUBMIT PLANS TO DEMONSTRATE COMPLIANCE WITH EMERGENCY</tspan>
<tspan dy="16em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">LIGHTING AND ENERGY CODE REQUIREMENTS. THE CONTRACTOR NEEDS TO PROVIDE THE</tspan>
<tspan dy="17em" fill="#2c5573" font-family="OpenGost Type B TT" font-size="3.441666666666667" x="2" y="2">ARCHITECT WITH COPIES OF ALL APPROVAL LETTERS.</tspan>