2022-07-22 11:08:08 -05:00

4.2 KiB
Raw Permalink Blame History

1Column_1Column_2
2APPLICABLE CODES:GENERAL: • BUILDING/DWELLING CODE IBC 2015 & AHJ AMENDMENTS EXISTING: ENERGY CONSERVATION: • INTERNATIONAL ENERGY CONSERVATION CODE 2015 & AHJ AMENDMENTS PLUMBING: MECHANICAL: • MECHANICAL CODE IMC 2015 & AHJ AMENDMENTS ELECTRICAL: • ELECTRICAL CODE NEC 2017 & AHJ AMENDMENTS FIRE: • FIRE/LIFE SAFETY CODE 2009 NFPA-1 & AHJ AMENDMENTS ACCESSIBILITY: • ANSI STANDARD A117.1-2009- FOR ACCESSIBILITY FUEL: • INTERNATIONAL FUEL GAS CODE 2015 & AHJ AMENDMENTS
3CHAPTER 3 USE AND OCCUPANCY CLASSIFICATION:310.4 RESIDENTIAL GROUP R-2
4SECTION 420 GROUPS I-1, R-1, R-2, R-3 AND R-4SECTION 420 GROUPS R-2 • FIRE PARTITIONS IN ACCORDANCE WITH SECTION 708 • HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
5CHAPTER 5 CLASSIFICATION OF WORK:NEW
6504.3 HEIGHT IN FEETR-2 TYPE VB (SPRINKLERED): • ACTUAL: 35FT • ALLOWED: 60FT
7504.4 NUMBER OF STORIESR-2 TYPE VB (SPRINKLERED): • ACTUAL: 3 • ALLOWED: 4
8506.2 ALLOWABLE AREA DETERMINATION & 506.3 FRONTAGE INCREASE: • TABULAR PER FLOOR AREA LIMIT PER CHAPTER 5 = 7000 SQ.FT. • ALLOW HEIGHT = 60 FT; ALLOW STORIES = 3 • NFPA 13 SPRINKLERS • COMPUTE AREA INCREASE DUE TO FRONTAGE: FRONTAGE COEFFICIENT, IF 0.589 • PERIMETER, P 354 FT • 'FRONTAGE' PERIMETER, F 306 FT • WEIGHTED AVERAGE DISTANCE FROM 'F' = 228.75 FT • COMPUTE ALLOWABLE PER STORY AREA, AA = AT +(NS X IF) = 25120.94 SQ.FT. • MAXIMUM ALLOWABLE AREA = AA X 3 = 75362.83 SQ.FT. • MAXIMUM NUMBER OF STORIES FOR GROUP R WITH NFPA 13R SPRINKLERS, PER SEC. 903.3.1.2.THIS CRITERIA IS MET, SO STORY LIMIT = 3 • THE REVISED ALLOWABLE HEIGHT IS 60 FT. ACTUAL • (ALL FLOORS): 16,826SF • FLOORS: 3
9508.3 NONSEPARATED OCCUPANCIES:N/A
10508.4 SEPARATED OCCUPANCIESN/A
11TABLE 601 FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)FOR TYPE VB STRUCTURAL FRAME: 0 HR BEARING WALLS- EXTERIOR: 0 HR BEARING WALLS-INTERIOR: 0 HR NON-BEARING WALLS-EXTERIOR (SEE TABLE 602) NON-BEARING WALLS-INTERIOR: 0 HR FLOOR CONSTRUCTION: 0 HR ROOF CONSTRUCTION: 0 HR
12TABLE 602 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCETYPE-VB FIRE SEPARATION DISTANCE • X < 5C = 1 HR • 5 ≤ X ≤ 10 = 1 HR • 10 ≤ X ≤ 30 = 0 HR • X ≥ 30 = 0 HR
13708.3 FIRE-RESISTANCE RATINGCORRIDORS: 1/2HR RATED DWELLING UNIT AND SLEEPING UNIT SEPARATIONS: 1/2HR RATED
14711.2.4.3 DWELLING UNITS AND SLEEPING UNITSBETWEEN DWELLING UNITS: 1/2HR RATED
15803.11 INTERIOR FINISH REQUIREMENTS BASED ON GROUPFOR SPRINKLERED R-2: INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS: CLASS C CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS: CLASS C ROOMS AND ENCLOSED: CLASS C
16SPRINKLERS (SECTION 903 AUTOMATIC SPRINKLER SYSTEMS):NFPA13 SPRINKLER THROUGHOUT PROJECT (R-2)
17SECTION 1020 CORRIDORSCORRIDORS: 1/2HR RATED SEE SECTION 1021 EGRESS BALCONIES FOR CORRIDOR RATING AT EXTERIOR WALL
18SECTION 1004 OCCUPANT LOADTABLE 1004.1.2 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT RESIDENTIAL: 200 GROSS
191006.2.1 EGRESS BASED ON OCCUPANT LOAD AND COMMON PATH OF EGRESS TRAVEL DISTANCE:FOR R-2 MAXIMUM COMMON PATH WITH SPRINKLER SYSTEM: 125FT MAXIMUM OCCUPANT LOAD OF SPACE WITH ONE EXIT: 49
20SECTION 1017 EXIT ACCESS TRAVEL DISTANCE:FOR R-2: 250 (W/SPRINKLER)
211020.4 DEAD ENDS:50FT (WITH NFPA13 SPRINKLERS)
22SECTION 1021 EGRESS BALCONIESEXTERIOR EGRESS BALCONIES SHALL BE SEPARATED FROM THE INTERIOR OF THE BUILDING BY WALLS AND OPENING PROTECTIVES AS REQUIRED FOR CORRIDORS. SECTION 1020 CORRIDORS 1020.1 CONSTRUCTION CORRIDORS SHALL BE FIRE-RESISTANCE-RATED IN ACCORDANCE WITH TABLE 1020.1. THE CORRIDOR WALLS REQUIRED TO BE FIRE-RESISTANCE-RATED SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS. EXCEPTIONS: CORRIDORS ADJACENT TO THE EXTERIOR WALLS OF BUILDINGS SHALL BE PERMITTED TO HAVE UNPROTECTED OPENINGS ON UNRATED EXTERIOR WALLS WHERE UNRATED WALLS ARE PERMITTED BY TABLE 602 AND UNPROTECTED OPENINGS ARE PERMITTED BY TABLE 705.8.
232902.1 MINIMUM NUMBER OF FIXTURESCLASSIFICATION & OCCUPANCY: --- R-2 • WATER CLOSETS: 1 PER DWELLING • LAVATORIES: 1 PER DWELLING • BATHTUBS/ SHOWERS: 1 PER DWELLING