Structural Design Criteria
Building Code and Design Basis
| Item |
Description |
| Building Code |
2015 International Building Code (IBC) with local amendments |
| Authority Having Jurisdiction |
City of Janesville, Wisconsin |
| Risk Category |
II |
Dead Load1111dsfasd
Dead loads are determined from the actual weights of materials and fixed service equipment. Typical assumed weights for assemblies are as follows:
| Assembly Type |
Dead Load (PSF) |
| Metal Panels |
3 |
| Curtain Walls |
10 |
| Stone or Brick Veneer |
40 |
| Adhered Stone or Brick |
10 |
| Single-Ply Membrane Roof with Insulation |
10 |
Equipment Loads
- Assumed loads for known equipment are shown on the structural drawings.
Any change in type, size, location, or weight of equipment must be reported to the Engineer of Record (EOR) for verification of the supporting members before shop drawing submission.
- Equipment loads include the weight of concrete pads or curbs, if applicable.
- For equipment not shown on the structural drawings, if the unit weight divided by its bearing area exceeds the specified live load for that location, the contractor must notify the EOR prior to shop drawing submission.
Suspended Ceilings and Mechanical Systems
| Item |
Allowance |
| Hanging Ceilings and Mechanical Equipment (ductwork, sprinkler piping, etc.) |
5 PSF |
Live Loads
Live loads shall be as indicated on the structural drawings and comply with the applicable sections of the IBC.
| Occupancy or Use |
Uniform |
Concentrated |
| Corridors |
100 psf |
- |
| Office Buildings - Corridors above first floor |
80 psf |
2,000 psf |
| Office Buildings - Offices |
50 psf |
2,000 psf |
| Stairs and exits |
100 psf |
300 psf |
| Roof - Ordinary, flat, pitched, or curved unoccupied roofs |
20 PSF |
300psf |
Snow Loadafasdasdfa
| Parameter |
Value |
| Ground Snow Load, Pg |
30 PSF |
Wind Design
| Parameter |
Value |
| Ultimate Design Wind Speed (Vult) |
115 mph (3-sec gust) |
| Nominal Design Wind Speed (Vasd) |
89 mph (3-sec gust) |
| Exposure Category |
II |
| Internal Pressure Coefficient |
± 0.18 |
| Components and Cladding Pressures |
See structural drawings and pressure schedule |
| Main Wind Force Resisting System |
Wood shear walls |
Rain Load
| Parameter |
Value |
| 100-Year Rainfall Intensity |
3.0 in/hr |
| Maximum Roof Rain Load |
0 PSF (i.e. no accumulation) |
| Maximum Rainwater Depth (Static + Hydraulic Head) |
0 in (i.e. no accumulation) |
Seismic Design
| Parameter |
Value |
| Geotechnical Report No. |
N/A - assuming min. soil bearing |
| Site Class |
D |
| Mapped Spectral Accelerations (SS, S1) |
0.11, 0.06 |
| Design Spectral Accelerations (SDS, SD1) |
0.099, 0.086 |
| Seismic Design Category (SDC) |
B |
| Design Base Shear |
XX% of Seismic Weight |